Toolbox 32 User Manual 1.47d www.cse-semaphore.com/mykingfisher
Page
IO Wiring
IO POWERED BY LP-2/3
IO POWERED EXTERNALLY
ANALOG INPUTS* (0-20 or 4-20 mA)
ANALOG INPUTS* (0-20 or 4-20 mA)
GND / 0V
PWR
transmitter
PWR
24V OUT
24V OUT
transmitter
transmitter
PWR
+
250
250
250
POWER
SUPPLY
POWER
transmitter
transmitter
transmitter
ANALOG OUTPUT (LP-3 only)
ANALOG OUTPUT (LP-3 only)
24V OUT
Current Load
Current Load
POWER
SUPPLY
Current Load
DIGITAL OUTPUTS
#
DIGITAL OUTPUTS
#
DI / PULSE
DO6 DO5 DO4 DO3
GND
DI CH 7/DO CH 5
DI CH 5/DO CH 3
DI CH 6/DO CH 4
DO CH 1 COM.
DO CH 2 COM.
CPU 5V OUT
DI CH 8/DO CH 6
5V DI8 DI7 DI6 DI5 DI4 DI3
24V OUT
LOAD
DO CH 1 or 2
COM.
GND / 0V
LOAD
Relay
Output
(optional)
24V OUT
Relay
Output
POWER
Transistor
Output
(optional)
DIGITAL INPUTS
DIGITAL INPUTS
DI CH 1 or 2
FIELD CONTACT
DI CH x
5V OUT or
24V OUT or
VDC1 OUT
Pulse
Counting in
Subactive
Sleep Mode^
DI CH x
SUPPLY
GND / 0V
* When using a 0-5 V or 1-5 V analog input, the external 250
Ω
resistor is not required. Unused inputs should be tied to
GND / 0V to prevent spurious readings. 0-5 or 0-20mA is the default analog input range. 1-5 or 4-20mA is software
configurable.
#
DI Channels 5 to 8 can be software configured as transistor digital outputs. When the output is energised, the output is
shorted to the OV terminal.
^
CPU 5V Out
stays enabled during power down modes and can only be used with DI1 and DI2 to wake the RTU or to
count pulses while remaining asleep. Note:
CPU 5V Out
is not isolated.