Maxon MODMAX MM-6280IND Bedienungsanleitung Seite 253

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 306
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 252
Toolbox 32 User Manual 1.47d www.cse-semaphore.com/mykingfisher
Page
253
PC-1
Register
(ss = slot 1-64)
Raw
Scale
Eng. Units Read
Write
Description
#AI13.2 0-32640
0 to 32.27V Read PC-1 supply voltage
This voltage is either the 12V supply voltage or the
battery voltage. Note: the PC-1 is not AC powered.
#AI13.3 0-32640
-1 to +1A Read Battery charging current (positive when charging
battery)
#AI13.5 0-32640
-20 to +80 °C
Read Module temperature
#AI13.6 0-32640
0 to +2 A Read Supply current into the PC-1
#DI13.2 N/A N/A Read ON = Aux 24V Failure or Not Present
#DI13.3 N/A N/A Read ON = Battery Not Low, OFF = Battery Low
#DI13.11 N/A N/A Read ON = Battery is being charged
(Current into battery > 100mA)
#DI13.12 N/A N/A Read ON = Battery is being discharged
(Current out of battery > 60mA)
N/A N/A N/A Read AC mains fail *
Hardware Overview
* A PC-1 is powered by +12VDC and so cannot directly monitor AC mains power. To determine AC mains power fail, the
battery discharging input is monitored for when it is continuously ON for more than 30 seconds. An example of how to do
this is detailed in the topic Examples - Exception Reporting Digitals.
RT-1
Register
(ss = slot 1-64)
Raw
Scale
Read/
Write
Description
#AIss.1 to 4 0-32760
= -150 to
+400 °C
Read 4-channel Pt100 temperature input module with a standard
temperature range as shown. Note: other temperature ranges are
available.
Seitenansicht 252
1 2 ... 248 249 250 251 252 253 254 255 256 257 258 ... 305 306

Kommentare zu diesen Handbüchern

Keine Kommentare