Maxon MODMAX MM-6280IND Bedienungsanleitung Seite 181

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 306
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 180
Toolbox 32 User Manual 1.47d www.cse-semaphore.com/mykingfisher
Page
181
View - RTU Comms Statistics
Displays communication successes and fails for each remote RTU that the local RTU has communicated
with. Totals are reset when the RTU is warm started.
RTU1 Successes/Fails
RTU2
RTU2 Successes/Fails
RTU3 Successes/Fails
MASTER RTU1
RTU3
RTU1 Successes/Fails
Figure: RTU Comms Statistics Stored In A Small Network
A success is recorded when a valid message is received or when a reply is received to a message sent to an
RTU. A fail is recorded each time there is no reply to a message attempt within the timeout period. An
example of Comms Statistics logged by RTU1 for communications to RTU2 are shown below.
Note: Fails will be recorded if too many messages are initiated (eg. each scan of ladder logic) or if the RTU
does not wait long enough for a reply. To ensure the RTU waits until the message attempt has timed out,
please use the #YPSTnn.2 bit as detailed in the topic Example - Polling Data.
View - PC Comms Statistics
Displays communication successes and fails for all messages sent by Toolbox. Select the Reset button to
clear totals.
Seitenansicht 180
1 2 ... 176 177 178 179 180 181 182 183 184 185 186 ... 305 306

Kommentare zu diesen Handbüchern

Keine Kommentare